【分享】12种常见消防设备的养护

One
火灾自动报警系统
Automatic fire alarm system
对消防火灾报警控制器进行自检功能检查。
Perform self check function on fire alarm controller.
对可测量相关参数进行查看和记录,如回路电流等。
Inspect and record measurable related parameters, such as loop current, etc..
公共场所烟感器、温感器安装检查,与底座接触是否良好,外观是否洁净完好。
Installation of smoke detector and temperature sensor in public place, good contact with the base and clean appearance.
每次随机抽取不低于5%的烟感或温感,喷烟或加热后查视报警是否正确;
Smoke or temperature is not less than 5% at random. Check whether the alarm is correct after smoking or heating;
手动报警按钮,检查安装是否牢固,有无破损及丢失。
Manual alarm button, check the installation is firm, whether there is no damage and loss.
每次随机抽取不低于5%的手动报警按钮,进行模拟报警,测试报警功能是否正常。
Each time the random manual alarm button not less than 5% is used to simulate alarm and test alarm function is normal.
对楼层内各模块箱进行外观检查,外接线是否固定良好。
Visually inspect all modules in the floor, and make sure the external wiring is in good condition.
对联动控制柜上的按钮每次按10%的比例进行功能试验,控制功能正常。
The function of the button on the linkage control cabinet is tested according to the proportion of 10% per hour, and the control function is normal.
对火灾报警控制柜、联动控制柜等进行清扫除尘。线路松动,应进行紧固。对自检、消音、复位功能检查,主电源与备用电源切换、报警检查。
The fire alarm control cabinet and linkage control cabinet are cleaned and removed. The line is loose and should be tightened. Check the self checking, noise elimination and reset function, switch between main power supply and standby power, and check the alarm.

Two
风机及防火阀
Fans and fire dampers
断开主电源,挂上标示牌,检查电机接地是否良好。
Disconnect the main power supply, hang the sign and check whether the motor is grounded properly.
坚固各部分松动的螺丝及联轴器。
Firm each part of the loose screws and couplings.
检测电动机的绝缘电阻,检查主回路接触点。
Check the insulation resistance of the motor and check the contact point of the main circuit.
调整皮带松紧,手转皮带轮,观察转动是否良好。
Adjust the belt tightness, hand turn pulley, observe whether the rotation is good.
检查与更换各接合面间的垫片和密封填料。
Check and replace the gasket and sealing filler between the joint surfaces.
清洁电机及风滤器和机壳内部。
Clean the motor and the air filter and the inside of the housing.
向转动部位加润滑油,保证联轴器及轴承的灵活性及稳定性。
Add lubricating oil to the rotating parts to ensure the flexibility and stability of the couplings and bearings.
检查调节阀的机械开闭动作,开闭角度标志。
Check the mechanical valve opening and closing action, open and close angle sign.
手动开机测定三相电流值,检查指示灯电压、电流表,听查风机各部件运行声音。
Manual startup to measure the three-phase current value, check the indicator voltage and ammeter, and listen to the sound of each component of the fan.
对各遥控点的控制箱(含箱内元件)进行全面检查。
Conduct a thorough inspection of the control box (including components in the cabinet) of each remote control point.
连续三次停开机检查手动各点遥控的正确性、可靠性。
Check the correctness and reliability of manual remote control for three times.
连续运转5-7分钟验证风机运转正常。
Run continuously for 5-7 minutes to verify the normal operation of the fan.
检查各控制箱内的电器触点及各接线端子,如有烧损想象,拆下后用砂纸打磨,用螺丝刀逐个紧固各接线端子,端子无松动。
Check the electrical contacts and terminals of each control box. If there is a burn, imagine to use the sand paper after the disassembly, and fasten the terminal blocks one by one. The terminal is not loose.
检查排烟阀微动开关及内部接线端子,端子无松动,微动开关固定良好。
Check the exhaust valve, microswitch and the internal wiring terminal, the terminal is not loose, the micro switch is fixed well.
检查远控排烟阀复位按钮、导轮、钢丝、转轴,用油壶给导轮、钢丝、转轴加油,复位按钮控制无误、排烟阀开启灵活。
Check the remote smoke valve reset button, guide wheel, steel wire, shaft, used to guide wire, shaft, oil gas, the reset button control error free, open and flexible exhaust valve.
检查各送风口百叶窗,送风口百叶位置正确。
Check the air supply blinds, the air outlet, the shutter position is correct.

Three
应急照明及疏散指示灯
Emergency lighting and evacuation light
每3个月进行一次备用电池亮灯(半个小时),使电池放电后再充电,延长电池寿命;
Every 3 months, a standby battery is switched on (half an hour) to recharge the battery and prolong battery life;
检查出口指示灯玻璃面板有无划伤或破裂现象;
Check the exit indicator glass panel for scratches or breaks;
出口指示灯电源指示灯是否亮,如不亮,应立即修理;
Is the indicator light of the outlet indicator light on, and should be repaired as soon as possible?;
检查出口指示灯安装是否牢固;
Check that the exit indicator is securely mounted;
针对检查中发现的缺陷取下来进行修复,再装回原位;
For defects found in the inspection, take down to repair, and then loaded back in place;
灯箱外壳及面板擦抹干净。
The light box, shell and panel are wiped clean.

Four
灭火器
Fire Extinguisher
灭火器应设置在通风、干燥、清洁的地点,不得受到烈日的曝晒,不得接近热源或受剧烈振动。
Fire extinguishers shall be installed in ventilated, dry, clean places, shall not be exposed to the hot sun, and shall not be near the heat source or subjected to severe vibration.
灭火器悬挂地点的环境温度为-10℃~55℃。
The ambient temperature of the fire extinguisher hanging place is -10 DEG C, ~55 DEG C.
灭火器设置地点应位置明显,便于取用,并且不影响安全疏散,推车式灭火器与其保护对象之间的通道应畅通无阻。
The setting place of the fire extinguisher is obvious, convenient for taking, and does not affect safe evacuation, and the passageway between the pusher type extinguisher and the object to be protected shall be unimpeded.
对灭火器要经常进行检查,检查内容为:
Fire extinguishers should be inspected regularly:
①喷筒是否畅通(如堵塞要及时疏通);
Whether the spray drum is unblocked (such as blocking should be clear in time);
②压力表指针是否在绿色区域(如在红色区域要检查原因,检查后要重新灌装);
Whether the pressure indicator is in the green area (for example, in red area, the reason should be checked and refilled after examination);
③零部件是否完整(有无松动、变形、锈蚀、损坏);
Whether the parts are complete (whether it is loose, deformed, rusted or damaged);
④可见部位防腐层是否完好(轻度脱落要及时补好,明显腐蚀应送专业部门维修及进行耐压试验);
Can be seen whether the site anti-corrosion layer is good (slight shedding should be promptly repaired, obviously corrosion, should be sent to professional departments for maintenance and pressure test);
⑤铅封是否完好(一经开放,必须按规定再行充装,并作密封试验,重新铅封)。
The seal is intact (once open, must be in accordance with the provisions for the filling and sealing test, re seal).
按时进行定期检查、保养:每一季度检查一次喷嘴和喷射管有否堵塞、腐蚀损坏,刚性连接式喷筒是否能将其轴线回转,并可在任意位置停留,推车式灭火器的行车机构是否灵活,有否检验标志。检查完后在灭火器检查卡上签字。
Schedule regular inspection and maintenance: every quarter check a nozzle and the jet pipe clog, corrosion damage, rigid connection type spray cylinder can its axis stay at any position and driving mechanism, cart type fire extinguisher is flexible, there is no sign of. Check on the fire extinguisher check card after check.
灭火器由消防部门认可的专业公司进行灌装。
Fire extinguishers are filled by professional companies accredited by fire department.

Five
室内消火栓
Indoor hydrant
消火栓外检查:检查消火栓门关闭是否良好,锁、玻璃有无损坏,消火栓门封条是否完好;
Fire hydrant outside inspection: check fire hydrant door closed is good, lock, glass damage, fire hydrant door seal is intact;
随机抽取消火消火栓总数的10%测试,按消火栓报警按钮,消防中心应有正确的报警显示,检查箱内元件是否良好、有无脱落,消火栓内水龙头有无渗漏;
Random fire hydrant is 10% of the total test, according to the fire hydrant alarm button fire alarm display center should have the right, check the components are good, no loss, no leakage in the fire hydrant tap;
开消火栓门取出水带,仔细检查有无破损,如有应即修补或替换;检查有无发黑发霉,如有,应取出刷净、晾干;
Fire hydrant door, take out the hose, carefully check for damage, if there should be repaired or replaced; check for black, mildew, if any, should be removed clean and dry;
将水带交换摺边或翻动一次;
Fold, fold, or change the hose;
检查水枪、水带接头连接是否方便牢固、有无缺损,如有,立即修复,然后擦净在消火栓内放好;
Check the water gun, hose connection, whether it is convenient, firm, and there is no defect, if any, immediately repaired, and then wipe it in the fire hydrant put away;
查接口垫圈是否完好无缺,替换阀上老化的皮垫,将阀杆上油;
Check whether the interface washer replaced leather pad on the flawless and perfect, the valve stem oil aging;
检查修整全部支架,掉漆部位应重新补刷,同时油漆;
Check all the brackets and remove the paint areas should be re painted brush, while painting;
将消火栓箱内清扫干净,部件存放整齐后,锁上消火栓门,更换检查标签卡;
Clean the fire hydrant box, keep the parts in order, lock the fire hydrant door and replace the check tag card;
检查后在消防箱检查卡上签名,放置在消防箱内,并贴上公司统一印制的消防箱封条。
After checking, sign on the fire box check card, put it in the fire box, and affix the sealed box of the fire box printed by the company.

Six
室外消火栓
Outdoor hydrant
用专用消火栓扳手打开室外消火栓,要求阀门启闭灵活,不漏水。
Open the outdoor hydrant with a special hydrant wrench, and require that the valve be opened and closed flexibly and without leakage.
检查水流指示器动作灵敏度。
Check the sensitivity of the flow indicator.
检查水流指示器接线端子,触点无松动、锈蚀。
Check the current indicator terminals, no loose contact, corrosion.

Seven
自动喷淋系统
Sprinkler system
每季度检查一次各楼层喷淋末端压力表指示,按10%比例测试信号阀关闭信号指示,按30%进行放水试验,消防中心有信号显示。
Check the sprinkler pressure indicator at each floor once every quarter. Test the signal valve to close the signal according to the 10% scale. Test the water according to 30%. The fire center has a signal display.
每季度对湿式报警阀、雨淋阀进行放水试验,能启动喷淋泵、雨淋泵或水喷雾泵,水力警铃响亮。
Every quarter to wet alarm valve, rain valve for water test, can start the spray pump, rain pump or water spray pump, hydraulic alarm bells loud.
每季度检查喷淋头一次,表面无油灰、无渗漏。
A quarterly review of the spray head, no surface putty and no leakage.

Eight
防火卷帘
Fire curtain
启动防火卷帘门升降按钮,防火卷帘升降平稳,无阻滞。
Start fire shutter door lifting button, fire curtain roll up and down smoothly, no block.
检查控制箱内各电器触点及各接线端子,如有触点烧损现象,拆下后用沙纸打磨,用螺丝刀逐个紧固各接线端子,无松动。
Check the control box and the electrical contacts and the connection terminals, such as contact burning phenomenon, remove after using sandpaper, using a screwdriver by fastening the connection terminals, no loose.
每年检查一次机械部分,包括齿轮、锋条,如锈蚀用煤油清洗,然后加润滑油保护。
Check the mechanical parts once a year, including gears, front ends, such as rust, kerosene, and grease.

Nine
紧急事故广播
Emergency broadcast
检查各切换器、继电器的接线和触点,成件完整、牢固、接触良好,切换器灵活、可靠。
Check the switches, relays, wiring and contacts, complete, solid, good contact, switch flexible and reliable.
调节音量控制器,检查音量变化是否正常。
Adjust the volume controller to check that the volume changes are normal.
检查话筒及话筒放大器音量、音质是否正常。
Check microphone and microphone amplifier for volume and sound quality.
检查磁带机或 CD机的运转和音质是否正常,要求运转正常、音质良好。
Check the tape or CD players and sound operation is normal, normal operation, good quality requirements.
检查楼层呼叫控制器的开关工作是否正常,要求灵活、可靠。
Check whether the switch of floor call controller is working properly, and be flexible and reliable.

Ten
对讲电话系统
Intercom telephone system
检查各电器触点和接线端子,如有触点烧损现象,拆下后用沙纸打磨,用螺丝刀逐个紧固各接线端子,无松动。
Check all electrical contacts and terminals, such as contact burning phenomenon, remove after using sandpaper, using a screwdriver by fastening the connection terminals, no loose.
检查固定电话、插孔与主机的通话质量,要求音质清楚,无杂音。
Check the quality of call between the fixed telephone, the jack and the host, and request the sound quality to be clear and no noise.
检查主机按键是否阻滞,通断是否良好,要求按键无阻滞,通断良好。
Check whether the main key is blocked or not, whether the switch is good or not, and press the button without blocking.
拾壹
XXXI
联动控制柜
Linkage control cabinet
控制柜上电源指示灯及各类开关检查,要求电源指示正常,开关处于开启或自动状态。
Check the power indicator and all kinds of switches on the control cabinet, and require the power supply to be normal. The switch is in the open or automatic state.
控制柜内部各电器触点检查,如有烧损,拆下后用砂纸打磨,要求触点完好、无松动。
Check the electrical contacts inside the control cabinet. If there is a burn, remove it with sandpaper, and make sure the contacts are intact and not loose.
检查各电器元件接线端子及端子排端子,用螺丝刀逐个紧固,各端子连接牢固、无烧损。
Check the wiring terminals and terminal blocks of each electrical component, tighten each other with a screwdriver, and make sure the terminals are firmly connected and without burning loss.
检查电源线、信号线,如有破损,用绝缘胶布包扎,如有老化更换。
Check the power cord and signal wire. If damaged, use insulating tape, if it is aged and replaced.
用毛刷、皮老虎对控制柜内部进行除尘。
Dust the inside of the control cabinet with a brush and a leather tiger.
拾贰
Twelve
气体灭火系统
gas fire extinguishing system
检查气瓶的称重装置或压力表指示,重量或压力正常。
Check cylinders for weighing devices or gauges indicating normal weight or pressure.
检查执行元件电磁阀、瓶头阀、分配阀,阀门无泄露,动作灵敏。
Check the actuator, solenoid valve, bottle head valve, distribution valve, valve no leakage, sensitive action.
气体控制箱进行模拟试验,报警、联动控制正常。
The gas control box is simulated, and the alarm and linkage control are normal.
瓶体及管路表面除尘。
Dust removing of bottle body and pipe surface.

联系方式

  1. 公司名称:XXX
  2. 电话:XXX
  3. 手机:XXX
  4. 联系人:XXX
  5. 地址:XXX

版权 © 上海通风管道匠心加工厂 网址:xiaofang.71ix.com  推荐:上海通风管道,上海螺旋风管,上海不锈钢风管